TW Filter Drier
The complete solution to reduce warranty repair costs and reduce service callbacks – TW Filter Drier with Spectroline AR-GLO®
The pre-charged TW Filter Drier is the only filter drier that exceeds industry standards with the Spectroline AR-GLO® tracer wafer pre-installed, and it is approved by all leading compressor and refrigerant manufacturers. The dye is compatible with all refrigerants to provide complete protection for 6-ton* air conditioning systems and it can be completed with the system running, eliminating downtime.
With the tracer wafer installed in the TW Filter Drier, the days of handling liquid dyes, getting false leak indicators and long, tedious leak searches are gone! The tracer wafer is placed in with the desiccant. When the system is started, the lubricant dissolves and circulates it throughout the refrigerant. If there is a leak, the dye will leave a mark where the refrigerant is leaking. The exact point of the leak is visible by a UV flashlight and looking through fluorescence-enhancing safety glasses. After the repair, wipe the dye using Glow Away or similar cleaner.
*NCH083-S-TW-R22-410A
Frequently Asked Questions
Q. What is Fluorescent Leak Detection?
A. Spectronics Corporation invented fluorescent leak detection in 1955, this technology is used by HVAC professionals worldwide to locate fluid leaks in air conditioning and refrigeration systems. This process is simple and effective requiring nothing more than fluorescent dye and a UV lamp.
Q. How does Fluorescent Leak Detection work?
A. First, add dye to the system and let it circulate. The dye/oil mixture escapes with the refrigerant and collects at all leak sites. Next scan the system with an ultraviolet lamp and see all leaks glow brilliantly!
Q. I am nervous about voiding my equipment’s warranty if I add dye. What should I consider when choosing a dye?
A. Spectroline dyes are the only highly concentrated dyes in the industry that are approved by manufacturers, co-solvent free, NSF certified and can remain safely in systems for its lifetime. Spectroline is the only manufacturer with OEM approval from companies such as Copeland, Bristol, Whirlpool, Carrier, Embraco and many more.
Q. How much dye should be added to the system?
A. 4 ml of dye is enough to treat 2 L of lubricant, 6 kg of refrigerant or 5 tons of cooling capacity. A complete dosage chart is included with all our dyes.
Q. What types of leaks can be found using Spectroline products?
A. All leaks, including leaks as small as 3 ml per year and intermittent leaks that only appear when the system is under pressure.
Q. Are Spectroline AR-GLO ® dyes compatible with all refrigerant and lubricants, including R-410a?
A. Yes. Spectroline AR-GLO® fluorescent dye is a universal (POE) that works with all refrigerant gases and lubricants.
Q. Does the air conditioning system need to be evacuated or can you find leaks while it is running?
A. The system does not need to be evacuated. The dye can be used at any time the system is running.
Q. How long does it take to find a leak?
A. In a smaller system, you can find leaks in seconds. In larger systems, in supermarkets for example, it may take a few hours. Our recommendation is to use TW Filter Drier with Spectroline AR-GLO when a new installation 1n is performed. In this way, the technician can do a weekly or monthly leak detection inspection in seconds.